HBM Device Failure… continued
According to S20.20, either personnel to ground resistance should be less than 35 MΩ or the footwear-floor combination shall generate less than 100 V. The essence of S20.20 is to protect devices to 100 V.If the footwear-floor combination does not generate more than 100 V, the system is adequate for use even if the body resistance to ground is greater than 35 MΩ. This allows for a great deal of ESD control flexibility, particularly since many organizations use ESD control footwear and floors but few offer a combined resistance to ground in the 1-MΩ to 35-MΩ range. If body voltage is the primary control element, the document requires that a proper measurement in accordance with ESD STM 97.2-1999 Floor Materials and FootwearVoltage Measurement in Combination With a Person confirms this level of performance. Measuring Body-Voltage Generation Measurement setup requires a charge plate monitor (CPM); an X-Y recording device; a long, high-quality test lead; and a few accessories. In effect, the operator will make several specific walking steps while connected to the CPM. The recorder documents the operator's generated walking voltage for later analysis. There are several instrument options for this measurement. You might use a standard 20-pF CPM or a portable system suitable for the measurement. Recording devices may be a strip-chart recorder, an X-Y plotter, or an analog-to-digital converter connected to a computer. |
|
|
Regardless of instrument selection, the measurement records a six-step walking pattern that provides data used for projecting two probable ranges of human body voltage generated in the following situations (Figure 2):
Figure 2: Six-Step Walking Pattern For Body-Voltage Generation Analysis. Maximum body voltage is generated with Steps 1 through 4. Minimum voltage is recorded when the operator pauses after Steps 5 and 6. |
![]() |
|
The six-step pattern compensates for the fact that everyone walks differently. Repetitive patterns provide relative data that can be statistically assessed to approximate the range of probable voltage generation experienced with any combination of footwear and floors. |
|
The walking pattern commences once the system is zeroed to its ground reference, then repeated approximately 20 times. Starting at the upper left corner of a 4-ft floor segment, the pattern begins with the operator stepping backwards with the left foot and basically continuing in a smooth, circuitous pattern back to the starting point, then pausing before commencing the next pattern. Each walking pattern is identified, and maximum and minimum absolute values are defined. Once the values are defined, there are three approaches to evaluating the data:
|
|
by Stephen A. Halperin, Stephen Halperin & Associates |
|






